Product Description
Benshaw Surprotex SPE22-3PR-22A Electronic Overload relay with selectable trip class from 5-30, AMP range from 4.4 to 22 AMPS, screw terminals and direct mounts to RSC contactors. Direct mount overload only mounts to RSC-9, RSC-12, RSC-18 and RSC-22 contactors.
AMP Range |
4 to 22 AMPS |
Trip Class | 5, 10, 20 or 30 |
Mounting |
Direct Mount |
Phase loss protection | Yes |
Terminals | Screw |
Mounts to |
RSC-9, RSC-12 RSC-18, RSC-22 |
Benshaw offers the SPE overload relay series for complete electronic motor protection in a small frame size. These solid state overloads can mount directly to the load side of any 3 pole contactor from 9 to 22 AMPS while providing over current and phase loss protection. The wide AMP range reduces inventory costs where one overload relay will cover the possible AMP ranges of more than 5 of its thermal overload counterparts.