Product Description
Eaton XTPB001BC1 manual motor protector that is adjustable from 0.63 to 1 AMP, has Class 10 tripping characteristic (trips in 10 seconds or less), push button on/off operation and mounts on standard 35MM DIN rail. This motor starter is permissible for use as a thermal magnetic circuit breaker for use in many domestic and international applications and is also classified as a manual motor protector for simple starting and stopping of motors (though a separate short circuit device must be installed upstream). Commonly you will find the XTPB001BC1 in group motor installations or combined with a XTCE contactor to form a Type E Self Protected combination starter.
| AMP Range | 0.63 to 1 AMP | 
| Trip Class | 10 (10 seconds or less) | 
| Terminals | Screw | 
| Mounting | DIN rail | 
| On/Off | push button | 
Product Description
Eaton’s new XT family of manual motor protectors (MMPs) features a pushbutton or rotary ON/OFF manual disconnect, Class 10 adjustable bimetallic overload relay and fixed magnetic short-circuit trip capability in one compact unit. Two frame sizes are available: Frame B (45 mm) for motors with FLA ratings up to 32A and Frame D (55 mm) covers motor FLA ratings up to 65A. 
FEATURES:
 - Adjustment dial for setting motor FLA
 - DIN rail mount
 - Terminal types available:
 - Screw terminals
 - Screw (line) and spring cage (load) terminals
 - Spring cage terminals
 - Accessories include:
 - Front and side auxiliary contacts
 - Trip indicating contacts
 - Tamperproof cover for OLR dial
 - Undervoltage release
 - Shunt trip
 - Through-the-door operators
 - Enclosures
 - Three-phase line side connecting links<BR
 
             
                     
                     
                     
               
               
          