Product Description
Eaton XTCERENCOILFT replacement coil rated at 24v50/60Hz for 3 pole XTCE080F and XTCE095F contactors. This coil comes with two plastic barriers to connect the coil feeders to the top unit of the contactor and can be easily replaced. Replacing the XTCERENCOILFT is simply done by using a screwdriver to remove the four screws on the bottom of the base which releases the top of the contactor from the base. Once separated, use a star tipped driver to remove the screws on either side of the coil which will release the silver brackets so that the coil and armature can be removed and replaced. The last step is to reconnect the top of the contactor to the base but ensure that the springs coming off the coil line up with the tabs on the underside of the top portion of the contactor.
Click here for a PDF file on this Eaton XTCEREN replacement coil
Part number | XTCERENCOILFT |
Coil Voltage | 24 volt AC |
Frame Size | F |
Works with: | XTCE080F/XTCE095F |