Product Description
Eaton XTCERENCOILDA replacement coil rated at 110v50Hz/120v60Hz for 3 pole XTCE040D, XTCE050D and XTCE065D contactors. This coil comes with two plastic barriers to connect the coil feeders to the top unit of the contactor and can be easily replaced. Replacing the XTCERENCOILDA is simply done by using a screwdriver to remove the two screws on the bottom of the base which releases the top of the contactor from the base. Once separated, lightly pull the sides of the base away from the coil which releases 4 plastic tabs (2 on each side of the coil) to free up the coil and armature. Replace with the new coil and insert back into the base of the contactor, ensuring that the 4 tabs on the coil click back into the base. The last step is to reconnect the top of the contactor to the base but ensure that the springs coming off the coil line up with the tabs on the underside of the top portion of the contactor.
Click here for a PDF file on this Eaton XTCEREN replacement coil
Part number | XTCERENCOILDA |
Coil Voltage | 110/120 volt AC |
Frame Size | D |
Works with: | XTCE040D/XTCE050D/XTCE065D |