Product Description
Siemens 3RB2016-1SB0 class 10 solid state (electronic) overload relay for direct mounting on size S00 contactors (3RT1015, 3RT1016, and 3RT1017), is adjustable from 3A to 12A and has phase loss protection. The manual or automatic reset feature on this Sirius series relay helps handle nuisance tripping when automatic reset is enabled and prevents potential motor damage when set to manual. The 3RB2016-1SB0 overload comes with screw terminals for easy installation and can be separately mounted from the contactor with a DIN rail or base mounted bracket. If the same AMP range is needed but class 20 tripping is required, check out the 3RB2016-2SB0, which will trip in 20 seconds or less and prevent excessive relay tripping.
AMP range | 3 to 12 AMPS |
Protection | Class 10 (trips in 10 seconds or less) |
Phase Loss Protection | Yes |
Reset type | Manual or Automatic |
Mounts to | 3RT1015, 3RT1016, 3RT1017 |
Click here to view a Adobe PDF file on the 3RB Siemens Overload
The 3RB20/3RB21 solid-state overload relays have been designed for the protection of three-phase motors in sinusoidal 50/60 Hz voltage networks. The relays are not suitable for the protection of single-phase AC or DC loads. The 3RU11 thermal overload relay or the 3RB22/3RB23 solidstate overload relay can be used for single-phase AC loads. For DC loads the 3RU11 thermal overload relays are available. The devices are insensitive to external influences such as shocks, corrosive environments, ageing and temperature changes.
For the temperature range from –25 C to +60 °C, the 3RB20/3RB21 solid-state overload relays compensate the temperature according to IEC 60947-4-1. The 3RB20/3RB21 solid-state overload relays are suitable for the overload protection of explosion-proof motors with "increased safety" type of protection EEx e according to ATEX guideline 94/9/EC. The relays meet the requirements of EN 60079-7 (Electrical apparatus for potentially explosive atmospheres – Increased safety "e").
The 3RB20/3RB21 solid-state overload relays are designed for:
• Inverse-time delayed protection of loads from overloading
• Inverse-time delayed protection of loads from phase unbalance
• Inverse-time delayed protection of loads from phase failure
• Protection of loads from high-resistance short-circuits
(internal ground-fault detection only with 3RB21).
The 3RB20/3RB21 solid-state overload relays are set to the motor rated current by means of a rotary knob. The scale of the rotary knob is shown in amps. With the 3RB21 solid-state overload relay it is also possible to select the trip class (CLASS 5, 10, 20 or 30) using a second rotary knob and to switch the internal ground-fault detection on and off.